When a Samsung EHS heat pump stops and shows a three-digit number, the code tells you which protection tripped. This guide covers codes printed in Samsung’s installation manuals for the R32 Mono outdoor units (AE080/120/140BXYD**), the Tank Integrated Hydro Unit (AE200/260RNW**) and the MIM-E03 control kit. Check the data plate before relying on any code below: other Samsung ranges use different books.
Where the code appears
Samsung says error codes show on the outdoor unit’s main PCB display or on the wired remote controller LCD. On the tank hydro unit an LED also flashes and the code shows on the controller. Write the number down before you switch anything off.
Codes an owner can do something about
- 911 (flow switch open / low flow): not enough water flow. On the tank hydro unit this trips when flow stays below 7 L/min (outdoor units up to 9 kW) or 12 L/min (above 9 kW) for 30 seconds at start or 15 seconds while running. Check that isolating valves are open and the system pressure is normal, then call your installer if it returns.
- 912: flow detected while the pump should be off. Usually a hydraulic or sensor issue for the installer.
- 908 / 909: freeze-prevention protection. See our frost protection guide.
- 440: heating blocked because it is too warm outside. This is a protection, not a fault. The R32 Mono outdoor installation manual DB68-11904A-05 (AE080/120/140BXYDEG and BXYDGG, p46) lists 440 as heating forbidden when outdoor temperature is over 43°C. The MIM-E03 control kit manual DB68-08471A-09 (p48) lists the same code as heating blocked above 35°C, and that kit book includes AE080/120/140BXYD** among the outdoors it works with. Those two printed thresholds belong to those books; they are not two valid figures for every Samsung EHS system. We do not have a page that says which figure a Mono outdoor plus MIM-E03 system actually uses, so do not assume both apply. Use the table that matches the device showing the code, and give both manuals to your engineer if both units are fitted.
- 919: the disinfection (legionella) cycle did not reach or hold its target. Check the hot water and immersion settings with your installer.
- 973 (MIM-E03): water pressure error. Read the gauge and tell your installer the value.
Codes that need an engineer
- 201 / 202: communication faults between the control kit or indoor unit and the outdoor unit.
- 601, 602, 604, 607: wired remote communication errors.
- 439, 536, 554: refrigerant leak detection. Do not keep resetting the unit.
- 899–904, 916: water, zone, tank or mixing-valve temperature sensors.
- 907: pipe-rupture protection.
FAQ
Can I just reset a Samsung error code?
Switching off and on may clear a one-off trip, but the cause stays. Repeat codes, and any leak code, need a qualified engineer.
Why does my code not appear in this list?
Each Samsung book prints its own table. Use the manual for your exact model, or send the code and model to the assistant.
What to tell your engineer
- The indoor and outdoor model numbers from the data plates.
- The exact code, where it showed, and a photo of the screen.
- The pressure gauge reading and whether any valves were recently touched.
- What the system was doing: heating, hot water, defrost or starting up.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Samsung EHS R32 Mono outdoor unit installation manual DB68-11904A-05: p45–47 (printed = PDF). Official PDF
- Samsung EHS Tank Integrated Hydro Unit installation manual DB68-08367A-07: p51 and p53 (printed ENGLISH-51/53 = PDF). Official PDF
- Samsung EHS R32 Control Kit MIM-E03 installation manual DB68-08471A-09: p48–49 (printed = PDF). Official PDF
Related guides
- Samsung EHS Flow Rate and Water Temperature Limits
- Samsung EHS Frost Protection and Glycol Guide
- Samsung Heat Pump Servicing: UK Owner Guide
Safety first
Owners can read codes, check the pressure gauge and valves, and keep the outdoor unit clear. Electrical, refrigerant (R32) and internal work, and any installer settings, are for a qualified, F-gas certified engineer.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Samsung.