Mitsubishi Electric states that an annual inspection is required to ensure safe, long-term operation of Ecodan systems. This guide brings together the maintenance points in the FTC7 pre-plumbed cylinder manual, the owner operation manual, and service manuals OCH816 and OCH880 for R290 PUZ-WZ outdoor units.
Annual checks
- Annual maintenance checks on both the cylinder unit and the outdoor unit.
- Pressure relief valve (3 bar), PUZ-WZ: check every year by turning the knob manually. If the valve sticks, the expansion vessel could burst.
- Cylinder side: the cylinder manual’s commissioning checks include cleaning the strainer in the pressure reducing valve and briefly opening each relief valve to confirm water runs freely through the tundish. Your engineer can repeat these at a service.
- Water quality: pH 6.5–8.0, with calcium and chlorine each no more than 100 mg/L and iron/manganese no more than 0.5 mg/L (PUZ-WZ50–80 service manual).
Parts replaced on a schedule (PUZ-WZ)
OCH816 lists the pressure relief valve and air separator for replacement every 6 years, to avoid water leakage. Mitsubishi Electric says replacement and inspection should always be done by a competent person with relevant training and qualifications.
Owner checks between services
- Small drips from a relief valve: Mitsubishi Electric suggests twisting the valve cap until it clicks to flush dirt. Take care, because the water is hot. If it keeps dripping, the seal may need replacing, so call your installer.
- Water discharging from a relief valve: the system has overheated or over-pressurised. Switch off power to the heat pump and any immersion heaters, then contact your installer.
- Noisy pipework: try bleeding radiators. Call the installer if it persists.
- Keep the outdoor unit clear, and note any error code.
R290 outdoor units
PUZ-WZ outdoor units use R290 refrigerant. Refrigerant work must only be carried out by an engineer trained for flammable refrigerants.
FAQ
How often should an Ecodan be serviced?
Mitsubishi Electric calls for an annual inspection, with some parts on a 6-year replacement cycle for PUZ-WZ units.
Can I test the relief valve myself?
Only the cap-twist the owner manual describes for a dripping valve. Full checks are for your engineer.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Mitsubishi Electric Ecodan FTC7 pre-plumbed cylinder installation manual, library 5760: p3, p5 and p53 (printed = PDF). Official PDF
- Mitsubishi Electric service manual OCH816 (PUZ-WZ50/60/80, R290): p14, p21 and p22 (printed = PDF). Official PDF
- Mitsubishi Electric service manual OCH880 (PUZ-WZ85–140, R290): p14 (printed = PDF). Official PDF
- Mitsubishi Electric Ecodan cylinder/hydrobox operation manual (FTC7), library 4938: printed p9 (PDF p10). Official PDF
Related guides
- Ecodan Error Codes: PUZ-WZ Outdoor Unit Check Codes
- Ecodan Hot Water and Legionella Settings Explained
- Ecodan Flow Rates: FTC6 vs FTC7 Tables Explained
Safety first
Owners can use the main remote controller, check valves and keep the outdoor unit clear. Refrigerant, electrical and service-menu work is for a qualified engineer, and PUZ-WZ units use flammable R290, so they need an engineer competent with it.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.