Ecodan Error Codes: PUZ-WZ Outdoor Unit Check Codes

When an Ecodan reports a fault, Mitsubishi Electric’s owner manual gives one instruction: make a note of the error code and contact your installer. This guide explains common outdoor unit check codes, so you know what is behind them. It covers the R290 PUZ-WZ outdoor units in service manuals OCH816 (PUZ-WZ50/60/80) and OCH880 (PUZ-WZ85 to WZ140). Indoor unit codes in the P, E and L groups are listed in indoor unit books, not here.

Where codes show

  • On the main remote controller. Mitsubishi Electric says the indoor or outdoor unit is reporting an abnormal condition.
  • The outdoor controller board logs present and past codes for the engineer.

Common outdoor check codes

  • U1 – abnormal high pressure: the high-pressure switch operated while the compressor ran. Causes listed include short cycling of the outdoor unit, a dirty outdoor heat exchanger, a locked or faulty fan and clogged pipes.
  • U2: high discharge temperature, high compressor temperature or refrigerant shortage.
  • U3, U4: outdoor thermistor open or short circuit.
  • U8: outdoor fan motor abnormality.
  • UL: abnormal low pressure.
  • F3, F5, F9: pressure switch connectors open, detected at power-on.
  • E8, E9: indoor/outdoor communication errors.
  • EA, Eb, EC: connecting-wire miswiring, wrong unit count or start-up time over.
  • EE: incorrect connection. The outdoor unit is not receiving signals from the interface or FTC.

What an owner can check

  • The outdoor unit has clear airflow, with no leaves, snow or stored items. This is relevant to U1.
  • Heating system valves are open. Mitsubishi Electric lists closed valves as a cause of poor heating.
  • Note whether the code appeared at power-on or during running.

Don’t power cycle repeatedly or open panels. Pressure, refrigerant and wiring faults need an engineer.

FAQ

Can I clear an Ecodan error code myself?

Mitsubishi Electric’s owner instruction is to note the code and contact your installer. Engineers reset logs after service.

My code isn’t listed here. Why?

P, E and L codes come from the indoor unit and are documented separately. Other outdoor ranges, such as PUZ-WM, have their own service manuals.

What to tell your engineer

  • The outdoor model (for example PUZ-WZ80VAA) and your cylinder or hydrobox model.
  • The exact code and a photo of the controller.
  • Whether it happened at start-up, in heating, hot water or defrost.
  • Anything recently changed, such as valves, power or settings.

Manual references

Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.

  • Mitsubishi Electric Ecodan cylinder/hydrobox operation manual (FTC7), library 4938: printed p9 (PDF p10). Official PDF
  • Mitsubishi Electric service manual OCH816 (PUZ-WZ50/60/80, R290): p31–34 and p61 (printed = PDF). Official PDF
  • Mitsubishi Electric service manual OCH880 (PUZ-WZ85–140, R290): p1, p35–38 and p68 (printed = PDF). Official PDF