Low water flow is one of the most common reasons a Grant Aerona stops or runs poorly. The figures differ between Grant’s two current ranges, so this guide keeps them apart. It covers the Aerona³ R32 (HPID6/10/13/17R32) and the Aerona 290 (HPR2904–HPR290155).
Aerona³ R32 flow figures
- Minimum flow: 5, 10, 15 and 15 L/min for the 6, 10, 13 and 17 kW models.
- Rated flow at W35: 20.22, 32.16, 40.68 and 50.88 L/min.
- System pressure: 1–3 bar.
- Grant says flow should give an 8 K flow–return temperature difference, and commissioning should aim for about 8°C.
- Low flow can trip FU, the high-pressure switch. Grant lists a large flow–return difference among its causes.
Aerona 290 flow figures
- P01 trips when circulating flow is below 8.3 L/min, or the flow switch sees below 4.6 L/min.
- Grant’s causes are lack of water, a faulty flow switch, a blocked filter or air in the system.
- For balancing, Grant gives a ΔT of about 4 K and sets the bypass to 8.3 L/min.
- P01 is common at commissioning because of trapped air. Grant describes a pump purge to clear it, which is an installer task.
Owner checks
- Read the pressure gauge with the system cold. Grant’s 290 manual says to top up if it is below 1 bar, if your installer has shown you how.
- Make sure radiator valves and any isolating valves are open.
- Note whether the fault happens at start-up, in hot water mode or after work on the system.
- Ask your installer to check the magnetic filter, which can block over time.
When to call the installer
- The pressure keeps falling: this suggests a leak.
- P01, FU or a pump error keeps returning.
- Pipes knock or gurgle, which points to air.
FAQ
Why does my new Aerona 290 keep showing P01?
Grant says trapped air often causes P01 at commissioning. The installer can purge it.
Can I change the pump speed?
Pump settings are set at commissioning. Ask your installer to measure the flow and temperature difference.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Grant Aerona³ R32 installation instructions DOC 0136 Rev 2.4 (Feb 2024): p11 (printed = PDF), Table 2-1; p39 and p49 (printed = PDF); p55–56 (printed = PDF). Official PDF
- Grant Aerona 290 installation instructions DOC 0204 Rev 1.9 (Aug 2026): p49 (printed = PDF); p51–52 and p54, p57 (printed = PDF). Official PDF
Related guides
- Grant Aerona Error Codes: Aerona³ R32 and Aerona 290
- Grant Aerona Servicing: UK Owner Guide
- Grant Aerona Weather Compensation Explained
Safety first
Owners can check pressure, controls and the outdoor grille. Electrical, internal and refrigerant work is for a qualified engineer, and the Aerona 290 uses flammable R290, so it needs an engineer competent with it.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Grant.