Short cycling means the compressor starting and stopping many times an hour, for example 10 to 20 minute runs. Some cycling is normal, but a lot of it wastes energy.
Why some cycling is unavoidable
In mild weather, the house needs less heat than the heat pump’s minimum output:
- VWL 35/6 and 55/6: heat output 2.10 to 5.50 kW and 2.10 to 6.90 kW at A7/W35.
- VWL 75/6: 3.00 to 7.40 kW at A7/W35.
- VWL 105/6 and 125/6: minimum 5.40 kW at A7/W35 (maximum 12.50 kW and 14.00 kW).
How Vaillant decides when to start
Vaillant heat pumps use an energy integral. Every minute, the gap between actual and target flow temperature is added up. The compressor starts when the set heat deficit is reached (factory setting Compr.start heat. from −60 °min) and stops when the deficit is repaid (integral = 0 °min). So the unit can keep running after the room reaches target, and pause even when it’s cold. That’s normal. The Live Monitor shows the energy integral.
Common causes
- The heat pump is oversized for the house (common with 10 and 12 kW units).
- TRVs or zones closing, which reduces water volume.
- Room temp. mod. Expanded switching the zone off.
- A heat curve or minimum flow set too high.
- Low flow from a blocked filter.
- Very short hot water runs.
What you can check
- Open TRVs and zones in main rooms.
- Check the curve isn’t too high.
- Compare compressor starts per day in the app or Live Monitor.
What your installer can do
Try Room temp. mod. Active rather than Expanded, adjust the compressor start integral, add a buffer or volumiser, or clean the filter.
FAQ
Is 20-minute cycling in spring a fault?
Not usually. It’s normal when demand is below the unit’s minimum output.
Will a lower curve reduce cycling?
Often, yes. A curve that’s too high is a common cause.
Related guides
Safety first
Owners can safely check pressure, valves, the controller and the outdoor unit from outside. Anything involving refrigerant, electrics, opening the unit or resetting internal cut-outs is a job for a qualified engineer. aroTHERM plus and aroTHERM pro units use R290, so refrigerant work needs an engineer competent with flammable refrigerants.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Vaillant.