Vaillant Heat Curve: Weather Compensation Settings

Weather compensation is the single biggest setting for comfort and running costs on a Vaillant heat pump. The controller uses a heat curve to set the flow temperature from the outdoor temperature.

How the Vaillant heat curve works

  • The curve is a number from 0.1 to 4.0 on the sensoCOMFORT. A higher number means hotter radiators at any outdoor temperature.
  • Each curve is drawn for a 20 °C room target. Raising the desired room temperature shifts the whole curve up, so on a Vaillant the desired temperature acts like an offset.
  • The factory curve for heat pump circuits is 0.60.

Vaillant’s starting points

Vaillant UK’s set-up guide (03/2024) says to set the curve from the design flow temperature where it’s known. Otherwise:

  • 0.8 to 1.0 radiators, new build.
  • 1.0 to 1.2 radiators, existing homes.
  • 0.6 to 0.8 underfloor heating.

Many owners end up lower after tuning.

Official example from the sensoCOMFORT manual

The printed heat-curve chart is drawn for a 20 °C room target. Vaillant’s example: heat curve 0.4 maintains a 40 °C flow temperature at -15 °C outside. Raising the desired room temperature shifts the whole curve (along the 45° axis shown in the manual).

How to tune it

  1. Start from the design figure on your MCS or commissioning paperwork (for example “45 °C at -3 °C”).
  2. Open TRVs fully in main rooms, so the curve controls the temperature, not the valves.
  3. Lower the curve in small steps of 0.05 to 0.1 every couple of days until rooms only just hold temperature, then go back up one step.
  4. Do the cold-weather tuning in properly cold weather.
  5. One cold room while the rest are fine is a balancing or radiator size issue, not the curve.
  6. Change one thing at a time and give it a day or two. Underfloor heating reacts slowly, so change it weekly.

Settings that work with the curve

  • Min. target flow temperature (factory 15 °C): a floor.
  • Max. target flow temperature (factory 55 °C): a ceiling. Vaillant suggests design flow plus 5 °C.
  • OT switch-off threshold (factory 16 °C): above this outdoor temperature, heating stops.
  • Set-back mode Eco or Normal: Normal holds a lower temperature outside your time periods, which usually suits heat pumps better.
  • Room temp. mod.: see our separate guide.

These are installer-level settings on the controller.

Changing it from your phone

The myVAILLANT app’s weekly planner can change heating schedules remotely. The heat curve, minimum flow and outdoor switch-off threshold are installer-level settings on the sensoCOMFORT; ask your installer to change them unless they have shown you another route on your system.

FAQ

It’s fine in cold weather but chilly in mild weather. Why?

That’s common with pure weather compensation. Options include raising Min. target flow a few degrees, a small curve change, or changing Room temp. mod. Talk to your installer about installer-level changes.

What’s the “right” curve for my house?

There isn’t one number. Many well-set-up radiator systems run on curves around 0.4 to 0.8, and underfloor often lower.

Related guides

Safety first

Owners can safely check pressure, valves, the controller and the outdoor unit from outside. Anything involving refrigerant, electrics, opening the unit or resetting internal cut-outs is a job for a qualified engineer. aroTHERM plus and aroTHERM pro units use R290, so refrigerant work needs an engineer competent with flammable refrigerants.