The Vitotronic 200 type WO1C controller was used with Vitocal 100-S/111-S, 200-A/222-A, 200-S/222-S, 300-A (AWO-AC 301.B and AWO 302.B) and 222-G/333-G. It shows two-character messages, not the F.xx codes of newer models. Older WO1A and WO1B controllers have their own books, so check the type on your controller.
Common messages
- 10 (outside temperature sensor): short circuit. The controller uses −40 °C as the outside value, so it will heat as if it were very cold. For an engineer.
- A9 (heat pump): the compressor is switched off, and heating and hot water rely on other heat sources if fitted. It can follow repeated pressure, flow-switch or defrost events. Viessmann says to switch the appliance off and on again after the fault is fixed.
- AA (cancel defrost): the flow or return temperature was too low during defrost. The compressor stays off until the secondary flow reaches 15 °C. Viessmann’s remedy is for an engineer and can involve adding a buffer cylinder.
- C5 (Power-OFF): your electricity supplier’s power-off signal is active. Viessmann says no action is needed unless it stays on.
- C9 (refrigerant circuit, SHD): the safety high-pressure switch has tripped, or the fan or primary pump is faulty. For an engineer.
- D3 (low pressure): a low-pressure fault in the refrigerant circuit, for example a blocked fan or a dirty evaporator. For an engineer.
- D6 (flow switch): the minimum flow rate in the heating circuit was not reached. Check the system pressure, and ask an engineer to check the flow rate.
FAQ
My Vitotronic 200 shows A9. What does it mean?
A9 means the heat pump has switched the compressor off after a fault or repeated events. Note any other messages and call your engineer.
Is C5 on my Vitotronic 200 a fault?
C5 means a power-off signal from the electricity supplier is active. Viessmann says no action is needed unless it stays on.
What to tell your engineer
- The Vitocal model and the controller type (WO1A, WO1B or WO1C) from the type plates.
- The exact message and a photo of the display.
- Your system pressure reading.
- When it happened: heating, hot water, defrost or start-up.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Viessmann service instructions Vitotronic 200 type WO1C, 6020389 (11/2023): message overview, 10 p77, A9 and AA p91, C5 p94, C9 p95, D3 p97, D6 p98 (printed = PDF). Official PDF
Related guides
- Viessmann Vitocal 100-A E Error Codes Explained
- Viessmann Vitocal 150-A and 250-A Fault Messages
- Viessmann Vitocal Maintenance and Safety for Owners
Safety first
Owners can read messages and check the pressure gauge. Refrigerant circuit messages such as C9 and D3 are for a qualified engineer only.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Viessmann.