Viessmann Vitotronic 200 (WO1C) Owner Settings

Older Vitocal Heat Pumps use the Vitotronic 200 type WO1C controller, with a Standard menu and an Extended menu. Its menus and factory values differ from the newer 7-inch touchscreen, so use this page only if your controller says WO1C.

Heating curve

Go to Extended menu, then “Heating” (or “Heating/cooling”), choose the circuit, then “Heating curve”, then “Slope” or “Level”. Viessmann’s factory settings are Slope 0.6 and Level 0 for heating, and Slope 1.2 and Level 0 for cooling. Your installer may have changed them.

  • Too cold in winter: raise the Slope one step. Too warm in winter: lower it one step.
  • Too cold in spring, autumn and winter: raise the Level. Too warm: lower the Level.
  • Too cold in spring/autumn but fine in winter: lower the Slope one step and raise the Level.
  • Too warm in spring/autumn but fine in winter: raise the Slope one step and lower the Level.

Hot water temperatures

  • “Set DHW temperature”: factory setting 50 °C. Used in normal hot water time phases.
  • “Set DHW temperature 2”: factory setting 60 °C. Used in “Temp. 2” time phases, for once-only hot water heating and in manual mode. The electric booster heater may need to be enabled to reach it.
  • The factory hot water time program runs all day, every day. Your rooms are not heated while the cylinder is heating.

Short-term changes

  • Party mode: heats to a temporary room temperature. It ends after 8 hours, when the time program switches to a “Standard” or “Fixd value” phase, or when you set it to OFF.
  • Economy mode: lowers the room temperature while you are out. It works only in the “Heating and DHW” or “Htg” operating program.
  • Heating off: choose “Only DHW”, or “Standby mode”, which keeps frost protection on.

Messages on the display

The controller shows a Note, Warning or Fault. For a fault, the red fault light flashes. Write down the text and the code next to it, for example “Outside temp. sensor 18”, then acknowledge it as the menu shows. A fault that is not fixed comes back at 7:00 the next day. An information note such as “Power-OFF C5” does not need a call.

Important: Viessmann says that if you acknowledge “Heat pump A9”, heating and hot water come only from backup electric heaters, which can be expensive. Ask your contractor to check the heat pump straight away.

FAQ

What are the factory heating curve settings on a Vitotronic 200 WO1C?

Viessmann’s operating manual gives Slope 0.6 and Level 0 for the heating curve. Your installer may have set different values for your home.

What hot water temperature does the Vitotronic 200 use?

The factory setting is 50 °C for the normal DHW temperature and 60 °C for DHW temperature 2, which is used for once-only heating and Temp. 2 time phases.

What to tell your contractor

  • Your Vitocal model and that the controller is a Vitotronic 200 WO1C.
  • The message text and code, and when it first appeared.
  • Any settings you have changed, with the old and new values.
  • Whether you have heating, hot water, both or neither.

Manual references

Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.

  • Viessmann operating instructions Vitotronic 200 type WO1C, 5817913 (11/2023): heating curve p29–30, Party and Economy mode p31–32, DHW p35–37, messages p56–57 (PDF pages). Official PDF

Related guides

Safety first

Changing settings in the menus is safe for owners. Leave anything behind the covers, refrigerant work and electrical checks to a qualified engineer.

Still stuck?

Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.

Independent guide, not affiliated with or endorsed by Viessmann.