Good flow through the heat pump keeps the Ideal Logic Air efficient and avoids the F27 no-flow fault. Ideal prints the key hydraulic figures for each model in the Installation and Maintenance manual UIN 241428. This guide lists them for the 4, 5, 8 and 10 kW units.
Flow figures by model
- Minimum flow: 8.5 L/min for 4 and 5 kW; 14.5 L/min for 8 and 10 kW.
- Design flow: 11.5, 14.3, 22.9 and 28.7 L/min for 4, 5, 8 and 10 kW respectively.
- Minimum copper pipe: 22 mm for 4/5 kW, 28 mm for 8/10 kW.
- Minimum free system volume: 24 L for 4/5 kW, 40 L for 8/10 kW.
- Filter mesh: 800 µm.
Pressure and temperature limits
- Maximum operating pressure 3.0 bar, minimum system pressure 0.5 bar. Commissioning fill is 1–1.5 bar.
- Expected expansion vessel pre-charge 1–1.5 bar.
- Table 1 gives a maximum flow temperature of 60°C. Table 9 lists maximum water temperature 65°C and minimum 17°C.
Cold start and frost behaviour
The heat pump will not start with primary water below 17°C. A backup heater warms it to 22°C first. Frost protection also uses the backup to reach 22°C when the condenser is at or below 4°C. So a slow first start on a cold system is expected.
When rooms are not warm enough
- Check the pressure gauge against the commissioning fill.
- Make sure radiator valves and any zone valves are open.
- Remember hot water has priority: heating pauses while the cylinder reheats.
- If it is only poor in cold weather, the weather compensation curve may need adjusting. That is an installer setting.
- Ask your installer to clean the filter and check the flow rate at the service.
FAQ
Why is my Logic Air not heating straight away?
If the water is below 17°C, the backup heater must lift it to 22°C before the heat pump starts. Hot water priority can also delay heating.
Can I turn up the pump speed?
No. Flow is set at commissioning against the design figures above. Ask your installer.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Ideal Logic Air Installation and Maintenance manual UIN 241428: p8 (printed = PDF), Table 1; p23–25 (printed = PDF), Table 9; p50 (printed = PDF). Official PDF
Related guides
- Ideal Logic Air Fault Codes: What Owners Can Check
- Ideal Logic Air Weather Compensation Explained
- Ideal Logic Air Servicing: UK Owner Guide
Safety first
Owners can use the controls, read alarms, check pressure and keep the outdoor unit clear. Refrigerant work needs a Category I or II F-gas engineer, and electrical, internal and installer-level settings are for a qualified engineer.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Ideal.