Weather compensation lets the Ideal Logic Air lower its flow temperature in mild weather and raise it when it is cold, which keeps it efficient. This guide explains what Ideal’s Installation and Maintenance manual UIN 241428 says about it. It is about the heat pump’s own settings, not Halo Air menus.
How it works on the Logic Air
- An outdoor sensor (QAC34) is permanently enabled, so weather compensation is always the basis of control.
- A heating curve maps outdoor temperature to flow temperature. Ideal prints gradients from 0.25 to 3: low curves suit underfloor heating, higher curves suit standard radiators.
- With weather compensation alone, the heat pump ignores room temperature.
Default settings Ideal prints
- Heating curve (720): 1.40 for radiators, 0.9 for underfloor.
- Curve offset (721): 0.
- Summer/winter limit (730): 21°C.
- Minimum flow (740): 17°C. Maximum flow (741): 55°C.
- Room influence (750): 20%.
Adding room compensation
Combined weather and room compensation needs a Halo Air room thermostat. Room influence runs from 1 to 99%. Ideal suggests 20% for radiators and 30–40% for underfloor. The reference room should not have TRVs.
Who can change it
Changing the compensation curve needs installer access on the control box, so ask your installer. Ideal’s user guide also lists checking the heating curve in its troubleshooting steps.
Signs the curve needs adjusting
- Rooms cold only in cold weather suggests the curve is too low.
- Rooms too warm in mild weather suggests the offset or curve is too high.
- Make one change at a time and give it a day or two.
FAQ
Why won’t my heating come on on a mild day?
Above the summer/winter limit (21°C by default) space heating is held off. This is normal.
Should my reference room have a TRV?
Not when room influence is used. Ideal says no TRVs in the reference room.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Ideal Logic Air Installation and Maintenance manual UIN 241428: p52 (printed = PDF), Table 15; p63 (printed = PDF); p67–68 (printed = PDF). Official PDF
- Ideal Logic Air Heat Pump User Guide UIN 235468 A07 (06/2024): p5 and p11 (printed = PDF). Official PDF
Related guides
- Ideal Halo Air Controls Guide for Logic Air Owners
- Ideal Logic Air Running Costs: Efficiency Checks
- Ideal Logic Air Flow Rates and Heating Checks
Safety first
Owners can use the controls, read alarms, check pressure and keep the outdoor unit clear. Refrigerant work needs a Category I or II F-gas engineer, and electrical, internal and installer-level settings are for a qualified engineer.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Ideal.