Ideal Logic Air Weather Compensation Explained

Weather compensation lets the Ideal Logic Air lower its flow temperature in mild weather and raise it when it is cold, which keeps it efficient. This guide explains what Ideal’s Installation and Maintenance manual UIN 241428 says about it. It is about the heat pump’s own settings, not Halo Air menus.

How it works on the Logic Air

  • An outdoor sensor (QAC34) is permanently enabled, so weather compensation is always the basis of control.
  • A heating curve maps outdoor temperature to flow temperature. Ideal prints gradients from 0.25 to 3: low curves suit underfloor heating, higher curves suit standard radiators.
  • With weather compensation alone, the heat pump ignores room temperature.

Default settings Ideal prints

  • Heating curve (720): 1.40 for radiators, 0.9 for underfloor.
  • Curve offset (721): 0.
  • Summer/winter limit (730): 21°C.
  • Minimum flow (740): 17°C. Maximum flow (741): 55°C.
  • Room influence (750): 20%.

Adding room compensation

Combined weather and room compensation needs a Halo Air room thermostat. Room influence runs from 1 to 99%. Ideal suggests 20% for radiators and 30–40% for underfloor. The reference room should not have TRVs.

Who can change it

Changing the compensation curve needs installer access on the control box, so ask your installer. Ideal’s user guide also lists checking the heating curve in its troubleshooting steps.

Signs the curve needs adjusting

  • Rooms cold only in cold weather suggests the curve is too low.
  • Rooms too warm in mild weather suggests the offset or curve is too high.
  • Make one change at a time and give it a day or two.

FAQ

Why won’t my heating come on on a mild day?

Above the summer/winter limit (21°C by default) space heating is held off. This is normal.

Should my reference room have a TRV?

Not when room influence is used. Ideal says no TRVs in the reference room.

Manual references

Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.

  • Ideal Logic Air Installation and Maintenance manual UIN 241428: p52 (printed = PDF), Table 15; p63 (printed = PDF); p67–68 (printed = PDF). Official PDF
  • Ideal Logic Air Heat Pump User Guide UIN 235468 A07 (06/2024): p5 and p11 (printed = PDF). Official PDF