The Ideal Logic Air heats a hot water cylinder as well as your radiators or underfloor heating. Ideal’s manuals explain how it chooses between the two and how it protects against legionella. This guide uses the Logic Air Installation and Maintenance manual UIN 241428 and user guide UIN 235468 A07.
Hot water takes priority
- The heat pump heats hot water when the cylinder drops below its setpoint minus a hysteresis.
- Hot water and central heating cannot run at the same time. Heating pauses while the cylinder reheats, which is normal.
Default target temperature
Ideal’s default hot water target (parameter 1610) is 50°C. A lower target that still meets your needs is usually more efficient, because the heat pump works harder as water temperature rises.
The legionella cycle
- Section 2.7.5 of the Installation and Maintenance manual (p23) and the user guide (p5) describe a weekly anti-legionella function that heats the cylinder to 60°C for 1 hour, using the DHW backup immersion or a boiler, and they refer to HSG274 Part 2.
- The same manual’s default settings table (Table 15, p52) lists parameter 1645 “Legionella funct setpoint” as 65°C, with 1642 Monday and 1644 11:00. Parameter 1640 is marked “set during Quick start”. Legionella protection is enabled as default (1 h/week).
- 60°C is the temperature in the written description; 65°C is the printed table default for parameter 1645. They are not two names for the same figure. Ask your installer which temperature your commissioned system uses.
Immersion boost
The user guide shows how to switch the immersion on from Special operations on the control box. It is direct electric heating, so use it for occasional top-ups rather than daily.
Using the Halo Air
The Halo Air menu includes a hot water view. Its timed hot water feature is disabled by default and is set up by the installer if needed.
FAQ
Why does my heating go off while the hot water heats?
The Logic Air can only do one at a time, and hot water has priority.
Can I turn the legionella cycle off?
Don’t. It is part of the safety regime the installer set up. Talk to them about the timing if it is inconvenient.
Why does the water get hotter once a week?
That is the scheduled legionella cycle.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Ideal Logic Air Installation and Maintenance manual UIN 241428: p23 (printed = PDF); p52 (printed = PDF), Table 15. Official PDF
- Ideal Logic Air Heat Pump User Guide UIN 235468 A07 (06/2024): p5 and p7–8 (printed = PDF). Official PDF
- Ideal Halo Air Single Zone Installation and Servicing manual UIN 234829 A06: PDF p15 and p17. Official PDF
Related guides
- Ideal Logic Air Running Costs: Efficiency Checks
- Ideal Halo Air Controls Guide for Logic Air Owners
- Ideal Logic Air Servicing: UK Owner Guide
Safety first
Owners can use the controls, read alarms, check pressure and keep the outdoor unit clear. Refrigerant work needs a Category I or II F-gas engineer, and electrical, internal and installer-level settings are for a qualified engineer.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Ideal.