Mitsubishi Heavy Industries prints the hydraulic limits for Hydrolution (HM) systems in installation manual PSC012D169A. They matter when a system short-cycles, raises high condenser alarms or won’t heat properly. Figures below are for the 60 and 100 size HSB, HMA and HMS indoor units with their matching FDCW…VNX outdoor units.
System limits (60 size: FDCW60VNX-A / FDCW60VNX-W)
- Maximum climate system pressure: 2.5 bar (0.25 MPa).
- Highest recommended supply/return: 55/45°C. Maximum in the system and indoor unit: 65°C.
- Minimum system volume: 50 L for heating and cooling, 80 L for underfloor cooling.
- Maximum flow: 0.29 L/s. Minimum flow at 100% pump speed: 0.12 L/s (VNX-A) or 0.09 L/s (VNX-W).
- Nominal heating flow: 0.29 L/s (ΔT 5 K).
System limits (100 size: FDCW71VNX-A, FDCW71VNX-W, FDCW100VNX-A)
- Maximum pressure 2.5 bar. Recommended supply/return 55/45°C.
- Minimum volume 50 L (71 models) or 80 L (FDCW100VNX-A).
- Maximum flow 0.38, 0.38 and 0.57 L/s. Minimum flow 0.19, 0.19 and 0.29 L/s.
- Nominal heating flow 0.38, 0.38 and 0.43 L/s.
HSB pipe connections
- Climate system supply and return: 22 mm (HSB60-W) or 28 mm (HSB100-W).
- Refrigerant liquid/gas: 1/4″ and 1/2″ (HSB60-W), 3/8″ and 5/8″ (HSB100-W).
- The indoor unit has no shut-off valves or safety valve. MHI says these must be installed in the circuit.
Design notes
- MHI recommends no more than 55°C supply and 45°C return at the lowest design outdoor temperature.
- An external circulation pump is needed if system pressure drop exceeds the available external pressure, with a bypass and non-return valve. Use an overflow valve if flow can’t be guaranteed.
Owner checks
- Open radiator thermostats fully in most rooms, as MHI advises, rather than choking them.
- Low system pressure: MHI’s tip is to top up the climate system, but ask your installer how first.
- The supplied ball valve has a particle filter that needs cleaning after installation.
FAQ
What pressure should my Hydrolution run at?
Below the 2.5 bar maximum. Your installer’s commissioning figure is the one to keep.
Why do I get high condenser alarms?
MHI lists low flow among the causes, alongside the heating curve and emitter size.
Manual references
Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.
- Mitsubishi Heavy Industries Hydrolution (HM) installation manual PSC012D169A: printed p23 (PDF p25); printed p27 (PDF p29); printed p37 (PDF p39). Official PDF
- Mitsubishi Heavy Industries Hydrolution (HM) user’s manual PSB012A016B (2024-08): EN-14, EN-37 and EN-38 (PDF p16, p39 and p40). Official PDF
Related guides
- MHI Hydrolution Alarms: RC-HY Status Lamp and Codes
- MHI Hydrolution Heating Curve and Weather Compensation
- MHI Hydrolution Servicing: UK Owner Guide
Safety first
Owners can use the RC-HY controller, read alarms and keep the units clear. Electrical, refrigerant (R32/R410A) and internal work is for a qualified engineer, so contact your dealer or installer.
Still stuck?
Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.
Independent guide, not affiliated with or endorsed by Mitsubishi Heavy Industries.