MHI Hydrolution Heating Curve and Weather Compensation

Mitsubishi Heavy Industries Hydrolution systems use a heating curve: the controller sets flow temperature from the outdoor temperature. MHI says the aim is an even indoor temperature in all weathers, and energy-efficient operation. This guide follows MHI’s user’s manual PSB012A016B for RC-HY20-W/RC-HY40-W controllers.

Curve slope (menu 1.9.1.1)

  • Curves are numbered 0 to 15. A higher number is a steeper curve, giving hotter water when it’s cold outside.
  • The default is 9. Curve 0 means you are using an “own curve” set in menu 1.9.7.
  • The best slope depends on your local climate, your emitters (radiators or underfloor) and the house’s insulation.
  • MHI says the curve is set at installation and normally won’t need further adjustment.

Curve offset (menu 1.1)

For fine adjustments, MHI says to offset the curve up or down rather than change the slope. Without a room sensor, the offset runs from −10 to +10 (default 0). The installation record shows the default curve offset and slope as 0/9.

Minimum and maximum flow line temperature

These cap the curve at each end. MHI notes underfloor systems normally have a maximum flow line temperature of 35 to 45°C. Check your floor’s limit with your installer or floor supplier.

MHI’s adjustment rules

  • Cold outside and too cold indoors: increase the curve slope by one step.
  • Cold outside and too warm: reduce the slope by one step.
  • Mild outside and too cold: increase the offset by one step.
  • Mild outside and too warm: reduce the offset by one step.
  • Wait 24 hours between changes.

Other models

A full-page reread of the Hydrolution EZY user’s manual PSB012A031A (PDF p9 / printed EN-7 and PDF p23 / printed EN-21) confirms the same menu numbers: 1.9.1 heating curve (offset/curve slope) default 0/9, and menu 1.9.1.1 range 0–15 with default 9. The detailed adjustment guidance above follows the HM user’s manual PSB012A016B. For other generations, check your own book.

FAQ

Should I change the slope or the offset?

Offset for small, all-weather changes. Slope only if the problem is mainly in cold weather.

My radiators have TRVs. Does that matter?

MHI says to open thermostats fully in most rooms, so they don’t fight the curve.

Manual references

Page numbers refer to the page printed in the manual unless marked as a PDF page. Check the manual that matches your data plate.

  • Mitsubishi Heavy Industries Hydrolution (HM) user’s manual PSB012A016B (2024-08): EN-6 (PDF p8); EN-13–14 (PDF p15–16); EN-16–17 (PDF p18–19). Official PDF
  • Mitsubishi Heavy Industries Hydrolution EZY user’s manual PSB012A031A: PDF p9 and p20–23. Official PDF

Related guides

Safety first

Owners can use the RC-HY controller, read alarms and keep the units clear. Electrical, refrigerant (R32/R410A) and internal work is for a qualified engineer, so contact your dealer or installer.

Still stuck?

Ask the Heat Pump Assistant with your model, controller and what your screen shows, and you’ll get an answer tailored to your system. If it’s time for a check-up or a fault needs hands-on attention, Book a Service. You can also browse all our Help Guides.

Independent guide, not affiliated with or endorsed by Mitsubishi Heavy Industries.