In the three Samsung manuals below, error 201 is printed as a matching communication fault. Error 202 is listed separately — and in two of those manuals it is marked as a 3-minute communication error.
Those lines belong to the books and models in the table. They are not a generic description for every Samsung wired controller or every tank-hydro display.
What each of these manuals prints
| Manual | Models named in that book | 201 | 202 |
|---|---|---|---|
| R32 Mono outdoor IM DB68-11904A-05, error table p45 | AE080/120/140BXYDEG and AE080/120/140BXYDGG | CONTROL KIT / Outdoor UNIT Communication Error (Matching Error) | CONTROL KIT / Outdoor UNIT Communication Error (no “3 min” on that line) |
| MIM-E03 control kit IM DB68-08471A-09, error table p48 | MIM-E03EN and MIM-E03CN | CONTROL KIT/OUTDOOR UNIT communication error (Matching error) | CONTROL KIT/OUTDOOR UNIT communication error (3 min) |
| TDM outdoor IM DB68-07002A-14, troubleshooting p47 | AE044/066/090/120/160MXTPEH and AE090/120/160MXTPGH | Hydro Unit / Outdoor Unit communication error(Matching error) | Hydro Unit / Outdoor Unit communication error(3 min) |
A matching error means the outdoor and the control kit or hydro unit are not communicating as a recognised pair. It is a prompt to give both model numbers to an engineer, not a full diagnosis and not a reason to swap indoor units yourself.
The wider Samsung error-code guide groups 201 and 202 together as communication faults. Use that overview for other codes; use this page when the display shows 201 or 202 on one of the systems above.
What an owner can check
Write down the exact three-digit number and any extra words on the screen. Note whether it appeared on a wired controller, a hydro-unit display or the outdoor PCB. Confirm the outdoor and indoor or MIM-E03 codes on the data plates, then leave the covers on.
FAQ
Is 201 worded the same on TDM Plus and on a MIM-E03 system?
Both of those books call 201 a matching error. The TDM outdoor table says “Hydro Unit / Outdoor Unit”; the MIM-E03 table says “CONTROL KIT/OUTDOOR UNIT”. Use the wording from the manual that matches what is installed.
Does the Mono outdoor table also say 202 lasts three minutes?
No. The Mono outdoor table on page 45 lists 202 as a control-kit / outdoor communication error without the words “3 min”. That “3 min” wording is printed in the MIM-E03 table (p48) and the TDM outdoor table (p47).
What to tell your engineer
- The exact code (201 or 202) and any extra words on the display.
- Where it showed.
- Full outdoor and indoor or MIM-E03 model numbers.
- Whether the system is TDM Plus (MXTp + TNW), R32 Mono (BXYD) with a MIM-E03 kit, or another combination.
Manual references
Page numbers are those printed in the manual unless marked as a PDF page.
- Samsung EHS R32 Mono outdoor installation manual DB68-11904A-05: error codes p45. Download R32 Mono outdoor manual DB68-11904A-05 (PDF)
- Samsung EHS MIM-E03EN/CN R32 control kit installation manual DB68-08471A-09: error codes p48. Download MIM-E03 manual DB68-08471A-09 (PDF)
- Samsung TDM outdoor installation manual DB68-07002A-14: troubleshooting p47. Download TDM outdoor manual DB68-07002A-14 (PDF)
Related guides
- Samsung Heat Pump Error Codes: EHS Owner Guide
- Samsung EHS Model Numbers: BXYD, TDM and RNW
- Samsung TDM Plus Outdoor and Tank Pairing Guide
- Samsung MIM-E03 Control Kit and Wired Controller Guide
Safety first
Owners can read the code and the plates. Communication wiring, option switches and live terminals are for a qualified engineer.
Still stuck?
Ask the Heat Pump Assistant. Include your brand, model or controller, and the full code or message on screen. If you need hands-on help, Book a Service. You can also browse all our Help Guides.