Samsung TDM Plus Outdoor and Tank Pairing Guide

TDM Plus is Samsung’s split system that pairs an MXTPEH or MXTPGH outdoor unit with a TNWTEH tank-integrated hydro unit. It is not the later R32 Mono (BXYD) outdoor plus an RNW tank.

The outdoor manual DB68-07002A-14 is titled for AE044MXTPEH, AE066MXTPEH, AE090MXTPEH, AE120MXTPEH, AE160MXTPEH, AE090MXTPGH, AE120MXTPGH and AE160MXTPGH. Its cover also says “Air to Water Heat Pump -Air to Air Heat pump” and mentions other air-to-air indoor families; those indoor ranges are not described here.

The indoor book DB68-08915A-04 is titled “TDM PLUS Tank Integrated Hydro Unit AE***TNWTEH” and lists AE200TNWTEH/EU and AE260TNWTEH/EU. Those are not AE200RNWMEG / AE260RNWMEG tanks.

KEYMARK pairs in the TDM tank manual

The tank manual’s KEYMARK table (printed ENGLISH-70 to ENGLISH-71) lists:

Outdoor Indoor Registration
AE044MXTPEH/EU or AE066MXTPEH/EU AE200TNWTEH/EU 011-1W0369
AE044MXTPEH/EU or AE066MXTPEH/EU AE260TNWTEH/EU 011-1W0370
AE090MXTPEH/EU AE200TNWTEH/EU 011-1W0372
AE090MXTPEH/EU AE260TNWTEH/EU 011-1W0373
AE090MXTPGH/EU AE200TNWTEH/EU 011-1W0375
AE090MXTPGH/EU AE260TNWTEH/EU 011-1W0376
AE120MXTPEH/EU, AE120MXTPGH/EU, AE160MXTPEH/EU or AE160MXTPGH/EU AE260TNWTEH/EU 011-1W0378

That table does not list AE120 or AE160 TDM outdoors with an AE200TNWTEH tank. The outdoor book uses 044, 066 and 160 as model-code digits, not as a heating-capacity table on this page.

How TDM Plus differs from R32 Mono plus RNW

R32 Mono outdoors (AE080/120/140BXYDEG or BXYDGG) connect as water-only monoblocs and, in the Mono KEYMARK table, can pair with RNW tanks or a MIM-E03 kit for space heating only. A TDM outdoor connects with refrigerant pipework to a TNW hydro unit. If the plates say BXYD and RNW, use the Mono guides instead of this page.

Communication errors on a TDM outdoor

The TDM outdoor troubleshooting table (printed page 47) lists 201 as “Hydro Unit / Outdoor Unit communication error(Matching error)” and 202 as “Hydro Unit / Outdoor Unit communication error(3 min)”. That wording names the hydro unit, not a MIM-E03 control kit. See the error 201 guide for the printed text in each of the three Samsung books that list these codes.

FAQ

Can I fit an RNW tank on a TDM outdoor?

The TDM tank KEYMARK table pairs MXTp outdoors with AE200/260TNWTEH units. It does not list RNW tanks.

Is a CNW indoor the same as TDM Plus?

The TDM PLUS tank book title is AE***TNWTEH. A public CNW installation manual is not among the files used here, so no CNW pairing is listed.

What to tell your engineer

  • The full outdoor code (MXTPEH or MXTPGH) and the indoor code (TNWTEH or otherwise).
  • Whether the indoor unit is a tank-integrated hydro unit or another indoor type from the outdoor book’s air-to-air lists.
  • Any 201 or 202 code, and whether it showed on the outdoor PCB or the controller.

Manual references

Page numbers are those printed in the manual unless marked as a PDF page.

Related guides

Safety first

TDM Plus uses refrigerant pipework between outdoor and indoor units. Refrigerant work is for a qualified F-gas engineer.

Still stuck?

Ask the Heat Pump Assistant. Include your brand, model or controller, and the full code or message on screen. If you need hands-on help, Book a Service. You can also browse all our Help Guides.