Vaillant aroTHERM Not Heating: Checks to Try First

Last reviewed: November 2026. Help for Vaillant aroTHERM plus owners in the UK.

Short answer

Start with the check Vaillant gives owners: if the aroTHERM plus will not start, see whether the power supply has been interrupted and, if needed, switch on the disconnectors it is connected to in the building. Then read any fault code on the indoor unit’s control, check the water pressure (Vaillant’s F.22 guidance uses a normal range of 1 to 1.5 bar) and look for snow, leaves or ice on the outdoor grilles. A short pause with a cloud of steam is usually de-icing. If your check does not work, Vaillant says to contact a competent person. Never open the casing.

Checklist of five owner checks for a Vaillant aroTHERM plus that is not heating
Five checks you can do without opening anything.

Is it really off, or just paused?

Before you treat it as a breakdown, rule out the normal pauses. Vaillant’s aroTHERM plus installation instructions explain that at outdoor temperatures below 5°C, condensation on the evaporator fins can freeze. The unit detects the frost and thaws it automatically at intervals by reversing the refrigeration circuit, using heat taken from the heating installation. While that happens the radiators can cool briefly.

The aroTHERM plus operating instructions say that if you see a cloud of vapour on the unit you do not have to do anything, because it can happen during thawing. Vaillant’s handover guide adds that you may see steam and water coming from the bottom of the unit and that the de-icing cycle should only last a few minutes. More detail is in Vaillant aroTHERM defrost.

A set-back period can also feel like “no heating”. Vaillant’s handover guide describes a comfort temperature with a set-back temperature 3 or 4°C lower, for example 21°C and then 18 or 17°C. Radiators that feel only warm are also normal on a heat pump: see Vaillant aroTHERM with radiators.

Two lists comparing a normal de-icing or set-back pause with signs of a fault that needs a closer look
De-icing and set-back periods can look like a fault for a few minutes.

Safe checks in order

  1. Power. Vaillant’s operating instructions say that if the product will no longer start up, check whether the power supply is interrupted and, if required, switch on all the disconnectors it is connected to in the building. Look for a tripped breaker too.
  2. The code. Read the display on the indoor unit’s control and write any code down exactly.
  3. Water pressure. Vaillant’s F.22 guidance uses a normal range of 1 to 1.5 bar. See F.022 low water pressure.
  4. The outdoor unit. Vaillant asks owners to keep snow off the air inlet and outlet grilles and to clear leaves and dirt from around the unit and from the ventilation grille below it. Do this by hand from outside. Never chip ice or pour hot water on it.
  5. The control. Check the operating mode, schedule and any absence or holiday setting on your system control or in the myVAILLANT app.
  6. Valves. Leave radiator and zone valves as your installer set them. Closing several can restrict flow.

If the check Vaillant describes does not fix it, the operating instructions say to contact a competent person.

Codes that often go with no heat

Codes and wording vary by model and software, so always use the full code from your display. These four appear on Vaillant’s UK heat pump fault-code page.

F.22: low water pressure

Vaillant says the pressure is below the normal range of 1 to 1.5 bar. A competent owner can slowly raise it into that range using the filling loop, at their own risk. If the gauge already reads more than 1 bar, Vaillant says it is a case for an engineer.

F.532: building circuit flow rate too low

Possible causes Vaillant lists include low pressure, a blockage or restriction, a blocked filter or Y strainer, poor balancing and air or debris in the circuit. Vaillant says this is a case for your installer in the first instance. See Vaillant low flow.

F.718: fan unit blocked

Vaillant says this is a case for an engineer. You can look for snow, ice or debris at the grilles from outside without opening anything. See F.718 fan blocked.

F.733: evaporation temperature too low

Vaillant lists a lack of servicing and dirt or debris blocking the external air heat exchanger among the causes and says it is a case for your installer in the first instance.

For any other code, use the aroTHERM plus error codes pillar and the status codes guide. Most S. codes are status messages, not faults.

Diagram of an outdoor unit linked by eBUS to the indoor unit control and an optional system control, both of which can show codes
Fault codes appear on the indoor unit’s control. A system control can show codes too.

Resets and when to stop

Vaillant’s fault-code page says resetting can often resolve a fault or get the heat pump working again for a while. Its handover guide says the reset returns the heat pump from the fault condition to standby and that you should note the fault reference and contact Vaillant if a code shows. Reset once, in the way your own manual describes. If the code returns, stop. Vaillant says a fault that reappears straight after a reset, such as F.731, is a case for an engineer.

In freezing weather

Vaillant’s instructions say to make sure the heating installation stays in operation during freezing conditions and that all rooms are sufficiently heated. Unless a frost-protected system separation is fitted, the product should be switched on and stay switched on. Vaillant’s handover guide also says heat pump systems should not be turned off completely, because a cold house takes more energy to bring back up to temperature.

When to call someone

Contact a competent engineer if the power check does not bring it back, if a code keeps returning, if the pressure keeps falling or if ice keeps building on the unit. Vaillant’s guarantee terms say that if the heat pump develops a fault you should contact your original installer or Vaillant’s service team. The aroTHERM plus uses R290 refrigerant, so never open the casing or work near the refrigerant circuit. For non-brand checks, see heat pump not working and heat pump help.

Use the chat above to ask a question about your heat pump. We do not pass your details on to installers.

FAQs

Why is my Vaillant heat pump running but the radiators are cold?

It may be de-icing. Vaillant’s instructions say that below about 5°C frost can form on the evaporator and is thawed automatically, using heat taken from the heating installation, so radiators can cool for a few minutes. A set-back period on your schedule, a low flow fault or low water pressure are the other common reasons. Radiators on a heat pump also feel cooler than on a boiler by design.

Where do I find the fault code on an aroTHERM plus?

Vaillant’s installation instructions say a fault code is shown on the display of the indoor unit’s control. A system control such as sensoCOMFORT can show codes too. Write the code down exactly, then look it up in our aroTHERM plus error codes guide.

Can I reset my Vaillant heat pump?

Vaillant’s fault-code page says a reset can often resolve a fault or get the heat pump working again for a while and points owners to their user manual for how to do it. Use only the reset your own manual describes and only once. If the code comes back, stop resetting and contact a competent engineer.

Should I switch the aroTHERM off when it is not heating properly in winter?

Usually not. Vaillant’s instructions say to keep the heating installation in operation during freezing conditions with all rooms sufficiently heated. Unless your system has frost-protected system separation, the outdoor unit should stay switched on. If you cannot keep it running, Vaillant says to have a competent person drain the installation.

Sources we checked

This is general guidance only. For faults or anything electrical, please contact a qualified heat pump engineer or Vaillant.

Ask My Heatpump is an independent help site. We are not affiliated with, endorsed by or sponsored by Vaillant or any other manufacturer named on this page.